Simulink Reference    
Look-Up Table

Approximate a one-dimensional function using the specified lookup method

Library

Simulink Look-Up Tables and Fixed-Point Blockset LookUp

Description

The Look-Up Table block computes an approximation to some function y=f(x) given data vectors x and y.

The length of the x and y data vectors provided to this block must match. Also, the x data vector must be strictly monotonically increasing after conversion to the input's fixed-point data type, except in the following case. If the input x and the output signal are both either single or double, and if the lookup method is Interpolation-Extrapolation, then x may be monotonically increasing rather than strictly monotonically increasing. Note that due to quantization, the x data vector may be strictly monotonic in doubles format, but not so after conversion to a fixed-point data type.

You define the table by specifying the Vector of input values parameter as a 1-by-n vector and the Vector of output values parameter as a 1-by-n vector. The block generates output based on the input values using one of these methods selected from the Look-up method parameter list:

To create a table with step transitions, repeat an input value with different output values. For example, these input and output parameter values create the input/output relationship described by the plot that follows:

This example has three step discontinuities: at u = -1, 0, and +1.

When there are two points at a given input value, the block generates output according to these rules:

The Look-Up Table block icon displays a graph of the input vector versus the output vector. When a parameter is changed on the block's dialog box, the graph is automatically redrawn when you click the Apply or Close button.

When the Show additional parameters check box is selected, some of the parameters that become visible are common to many blocks. For a detailed description of these parameters, refer to Block Parameters in the Fixed-Point Blockset documentation.

To avoid parameter saturation errors, the automatic scaling script autofixexp employs a special rule for the Look-Up Table block. autofixexp modifies the scaling by using the output look-up values in addition to the logged minimum and maximum simulation values. This prevents the data from being saturated to different values. The look-up values are given by the Vector of output values parameter (the YDataPoints variable).

Parameters and Dialog Box

Vector of input values
Specify the vector of input values. The input values vector must be the same size as the output values vector. Also, the input values vector must be strictly monotonically increasing after conversion to the input's fixed-point data type, except in the following case. If the input values vector and the output signal are both either single or double, and if the lookup method is Interpolation-Extrapolation, then the input values vector may be monotonically increasing rather than strictly monotonically increasing. Note that due to quantization, the input values vector may be strictly monotonic in doubles format, but not so after conversion to a fixed-point data type.
Vector of output values
Specify the vector of output values. The output values vector must be the same size as the input values vector.
Show additional parameters
If selected, additional parameters specific to implementation of the block become visible as shown.

Look-up method
Specify the lookup method. See Description for a discussion of the options for this parameter.
Output data type mode
You can set the output signal to a built-in data type from this drop-down list, or you can choose the output data type and scaling to be the same as the input. Alternatively, you can choose to inherit the output data type and scaling by backpropagation. Lastly, if you choose Specify via dialog, the Output data type, Output scaling value, and Lock output scaling against changes by the autoscaling tool parameters become visible.
Output data type
Specify any data type, including fixed-point data types. This parameter is only visible if Specify via dialog is selected for the Output data type mode parameter.
Output scaling value
Set the output scaling using radix point-only or [Slope Bias] scaling. This parameter is only visible if Specify via dialog is selected for the Output data type mode parameter.
Lock output scaling against changes by the autoscaling tool
If selected, scaling of outputs is locked. This parameter is only visible if Specify via dialog is selected for the Output data type mode parameter.
Round integer calculations toward
Select the rounding mode for the fixed-point output.
Saturate on integer overflow
If selected, overflows saturate.

Conversions and Operations

The Vector of input values parameter is converted from doubles to the input data type. The Vector of output values parameter is converted from doubles to the output data type. Both conversion are performed offline using round-to-nearest and saturation. Refer to Parameter Conversions in the Fixed-Point Blockset documentation for more information about parameter conversions.

Examples

Suppose the Look-Up Table block in the above model is configured to use a vector of input values given by [-5:5], and a vector of output values given by sinh([-5:5]). The following results are generated.

Look-Up Method
Input
Output
Comment
Interpolation-Extrapolation
1.4
2.153
N/A
5.2
83.59
N/A
Interpolation-Use End Values
1.4
2.153
N/A
5.2
74.2
The value for sinh(5.0) was used.
Use Input Above
1.4
3.627
The value for sinh(2.0) was used.
5.2
74.2
The value for sinh(5.0) was used.
Use Input Below
1.4
1.175
The value for sinh(1.0) was used.
-5.2
-74.2
The value for sinh(-5.0) was used.
Use Input Nearest
1.4
1.175
The value for sinh(1.0) was used.

Characteristics

Dimensionalized
Yes
Direct Feedthrough
Yes
Sample Time
Inherited from driving block
Scalar Expansion
No
Zero Crossing
No

See Also

Look-Up Table (2-D), Look-Up Table (n-D)


  Logical Operator Look-Up Table (2-D)